The IR5050 is a compact, lightweight, high-voltage insulation resistance tester capable of outputting up to 5 kV. Its unique measurement technology enables stable measurements of up to 10 TΩ.
Best suited for high-voltage insulation resistance testing, the IR5050 is equipped with advanced measurement technology that guarantees stable readings across a range of applications, including high-voltage cables, transformers, and motors. It also features an intuitive rotary knob for straightforward operation, enhancing its versatility and user-friendliness for diverse industrial uses.
The IR5050 offers specialized insulation diagnostic functions such as step and ramp voltage testing. It automatically displays results in indices like PI (Polarization Index), DAR (Dielectric Absorption Ratio), and DD (Dielectric Discharge), streamlining the diagnostic process.
Enhancing efficiency, the IR5050 comes with data memory, and options for wireless and USB connectivity. It facilitates real-time graph trending on mobile devices and enables quick report generation, simplifying data handling and documentation.
| Measurement parameters | • Insulation resistance • Leakage current • Voltage • Capacitance (DD function) |
|---|---|
| Max. rated voltage to terminals | 1000 V AC, 2000 V DC |
| Max. rated voltage to ground | 1000 V (CAT IV), 600 V (CAT III) |
| Operating temperature and humidity range | -20°C to 50°C (*1) (no condensation) |
| Storage temperature and humidity range | -25°C to 65°C (-13°F to 149°F), less than 80% RH (no condensation) |
| Dustproof/waterproof | IP40 (with protector attached, excluding terminals) IP65 (CARRYING CASE C0212) |
| Standards | EN61010 (safety), EN61326 (EMC), IEC 61557-1, IEC 61557-2 (Insulation resistance tester) |
| Power supply | • LR6 (AA) alkaline battery × 8 • HR6 (AA) nickel-metal hydride (NiMH) rechargeable battery × 8 |
| Continuous operating time (*2) | Approx. 5 hours without Z3210 installed; approx. 4 hours with Z3210 installed and using wireless communication |
| Dimensions and weight | 195 mm (7.68 in.) W × 254 mm (10 in.) H × 89 mm (3.50 in.) D, 1.7 kg (59.97 oz.) (including batteries) |
| Included accessories | Test lead L9850-01 ×1, Test lead L9850-02 ×1, Test lead L9850-03 ×1, Alligator clip L9851-01 ×1, Alligator clip L9851-02 ×1, Alligator clip L9851-03 ×1, Carrying Case C0212 ×1, LR6 Alkaline battery ×8, Instruction manual ×1, Operating precautions ×1 |
Directly record to SD cards or internal memory for weeks of continuous monitoring without data loss. [Placeholder text box for custom product feature highlights populated later]
Power Parameters is the official authorized Australian service and technical support facility. We provide traceable calibration, certified warranty repairs, scheduled maintenance, and genuine OEM parts from our climate-controlled laboratory in Westmeadows, Victoria, as well as on-site calibration across Australia.

Model: IR5050